Product short description:
  • 0 to 25.6KHz frequency input range
  • DC voltage or DC current output
  • DIN rail G or T mount
RSS
TWITTER
Visit Us
Follow Me
LINKEDIN
Share

These transmitters accept periodic or pulse waveform signals such as those originating from tachometers, magnetic transducers, and turbine flow meters, and provide a proportional process current or voltage output signal.

Models

250T: Loop-powered transmitter series
350T: DC-powered transmitter series
450T: AC-powered transmitter series

Performance Specifications

Input Ranges:
Frequency: span ranges 0 to 25.6KHz, field-selectable, direct coupled inputs, ±25mV to 150V RMS
Output Ranges:
DC Current: 4 to 20mA
DC Voltage: 0 to 5V or 0 to 10V

Power Requirements:
250T: 12 to 50V DC @ 20mA (loop-powered)

350T: DC Voltage Source
Output Range                Power
4 to 20mA                10 to 36V DC @ 30mA
0 to 5V                      10 to 36V DC @ 9mA
0 to 10V                12.5 to 36V DC @ 9mA

450T: 115V or 230V AC, ±10%, 50 to 60Hz
Output Range                 Power
4 to 20mA                  115V AC @ 0.050A
4 to 20mA                  230V AC @ 0.025A
0 to 5V, 0 to 10V       115V AC @ 0.020A
0 to 5V, 0 to 10V      230V AC @ 0.010A

Ambient Temperature Range:
Operating: -13 to 185°F (-25 to 85°C)
Storage: -40 to 185°F (-40 to 85°C)
Accuracy:
±0.1% of calibrated span. Includes repeat-ability, hysteresis, terminal point linearity, and adjustment resolution.
Ambient Temperature Effect:
Less than ±0.01% of output span per °F (±0.018% per °C)
(Specification includes the combined effects of zero and span over temperature)
Noise Resistance:
RFI: Less than ±0.5% ,of output span effect
EMI: Less than ±0.25% of output span effect
Noise Rejection:
Common Mode: 115dB at 60Hz, 100 ohm unbalance
Normal Mode: Not Applicable
Response Time:
Time for output to reach 98% of output span depends on jumper-selectable frequency range.
Range 1: 8.0 sec response time (98%)
Range 2: 5.0 sec response time (98%)
Range 3: 0.4 sec response time (98%)
Bandwidth: -3dB at 25,600Hz, typical
Output Compliance:
250T: RLOAD (max.) = (VSUPPLY – 12V) / 20mA
350T: RLOAD (max.) = (VSUPPLY – 2.5V) / 20mA
450T: RLOAD = 600 ohms

  • Excellent accuracy and stability ensure reliable measurements in harsh industrial environments
  • RFI and EMI resistance minimize the effects of environmental noise
  • 90% span adjustment enables precise application calibration
  • Quartz crystal time-base design improves temperature performance
  • Field-selectable time constants optimize output response time and ripple characteristics
  • Selectable threshold circuits accept uni-polar/bipolar inputs (0V bipolar, 1.5V unipolar)
  • Excitation/pull-up circuit adds flexibility
  • 1500V AC peak isolation (250V AC or 354V DC continuous) prevents ground loops
    • 250T models: Input isolated from output/power
    • 350T models: Input isolated from output and power. Output and power share a common
    • 450T models: 3-way isolation. Input, output, and power circuits are isolated from each other
  • Operating temperature range: -13 to 185°F (-25 to 85°C)

Manuals

250T-FQ1 User Manual (Log in to download the file)

350T-FQ1 User Manual (Log in to download the file)

450T-FQ1 User Manual (Log in to download the file)

Additional information

Weight 16 oz
Dimensions 12 × 13 × 3 in
Part Number

DIN Rail 3.0, DIN Rail 16.7

  • Description

    DIN Rail Strip, Type T

  • Features & Benefits

    • Excellent accuracy and stability ensure reliable measurements in harsh industrial environments
    • RFI and EMI resistance minimize the effects of environmental noise
    • 90% span adjustment enables precise application calibration
    • Quartz crystal time-base design improves temperature performance
    • Field-selectable time constants optimize output response time and ripple characteristics
    • Selectable threshold circuits accept uni-polar/bipolar inputs (0V bipolar, 1.5V unipolar)
    • Excitation/pull-up circuit adds flexibility
    • 1500V AC peak isolation (250V AC or 354V DC continuous) prevents ground loops
      • 250T models: Input isolated from output/power
      • 350T models: Input isolated from output and power. Output and power share a common
      • 450T models: 3-way isolation. Input, output, and power circuits are isolated from each other
    • Operating temperature range: -13 to 185°F (-25 to 85°C)
  • Specs & Data Sheets

    Manuals

    250T-FQ1 User Manual (Log in to download the file)

    350T-FQ1 User Manual (Log in to download the file)

    450T-FQ1 User Manual (Log in to download the file)

  • Accessories

  • Additional information

    Additional information

    Weight 16 oz
    Dimensions 12 × 13 × 3 in
    Part Number

    DIN Rail 3.0, DIN Rail 16.7